SG60KU-M
High Yield
- Max. efficiency 98.9 %, CEC efficiency 98.5 %
- Long-term overload at 1.1 Pn
- Up to 4 MPP trackers
Easy O&M
Grid Support
- Integrated string current monitoring function for fast trouble shooting
- Compact design and light weight for easy installation
- Plug-in design of fan and SPD, easy for on-site maintenance
Saved Investment
- Max. DC/AC ratio up to 1.5
- Integrated DC combiner box, DC/AC switch and DC/AC overvoltage protection
- Compliance with standards: UL1741, IEEE 1547, IEEE 1547.1, CSA C22.2 107.1-01
- Low/High voltage ride through (L/HVRT)
- Active & reactive power control and power ramp rate control
Technical Data
Input (DC) | |
Max PV input voltage | 1000 V |
Min. PV input voltage / Startup input voltage | 300 V / 300 V |
Nominal input voltage | 710 V |
MPP voltage range | 300 – 950 V |
MPP voltage range for nominal power | 550 – 850 V |
No. of independent MPP inputs | 4 |
Max. number of PV strings per MPPT | 4 |
Max. PV input current | 112 A (28 A / 28 A / 28 A / 28 A) |
Max. current for input connector | 12 A |
Max. DC short-circuit current | 200 A (50 A / 50 A / 50 A / 50 A) |
Output (AC) | |
Nominal AC power (at 45 ˚C) | 60000 W |
Max. AC output power at PF=1 (at 45 ˚C) | 66000 W |
Max. AC apparent power (at 45 ˚C) | 66000 VA |
Max. AC output current | 80 A |
Nominal AC voltage | 3 / N / PE or 3 / PE, 277 / 480 V |
AC voltage range | 422 – 528 V |
Nominal grid frequency / Grid frequency range | 60 Hz / 55 – 65 Hz |
THD | < 3 % (at nominal power) |
DC current injection | < 0.5 % In |
Power factor at nominal powe / Adjustable power factor | > 0.99 / 0.8 leading – 0.8 lagging |
Feed-in phases / Connection phases | 3 / 3 |
Efficiency | |
Max. efficiency / CEC. efficiency | 98.9 % / 98.5 % |
Protection | |
DC reverse connection protection | Yes |
AC short-circuit protection | Yes |
Leakage current protection | Yes |
Grid monitoring | Yes |
DC switch / AC switch | Yes / Yes |
DC fuse | Yes (positive and negative, 15 A) |
PV string current monitoring | Yes |
Arc fault circuit interrupter (AFCI) | Yes |
Overvoltage protection | DC Type II / AC Type II |
General Data | |
Dimensions (W*H*D) | 665*915*276 mm 26.2''*36.0''*10.9'' |
Weight | 70 kg 154.3 lb |
Isolation method | Transformerless |
Degree of protection | NEMA 4X |
Night power consumption | < 1 W |
Operating ambient temperature range | -25 to 60¡æ (> 45 ¡æ derating) -13 to 140 ¨H (> 113 ¨H derating) |
Allowable relative humidity range (non-condensing) | 0 - 100 % |
Cooling method | Smart forced air cooling |
Max. operating altitude | 4000 m (> 3000 m derating) 13123 ft (> 9843 ft derating) |
Display / Communication | Graphic LCD / RS485, Ethernet |
DC connection type | Screw clamp terminal (10 AWG, Cu or Al) |
AC connection type | Screw clamp terminal (2/0 AWG, Cu or Al) |
Compliance | UL1741, IEEE 1547, IEEE1547.1,CSA C22.2 107.1-01 |
Grid support | LVRT, HVRT, active & reactive power control and power ramp rate control |